Description
Insulation Resistance ranges: Model 3166
Test voltage: 1000V
Measuring range: 2000M
Mid-scale value: 50M
Output voltage on open circuit: Rated test voltage+20% -0%
Output short circuit current: 550A
Primary Effective Measuring Range: 2-1000M
Accuracy: -+5% of indicated value at primary effective measuring range
-+0.7% of scale length at 0 and
-+10% of indicated value at other measuring range
AC Voltage Warning
Warning range | 0-600V AC |
Accuracy | -+3% of |
Power supply: 4*1.5V battery type SUM-3, R6, AA or equivalent
- Overload protection: Insulation Resistance Ranges
- Model 3166: 1200V (DC+ACp-p) for 10 seconds
- AC Voltage Range- 720V (DC+ACp-p)
Withstand voltage: 3700V AC for one Minute between electrical circuit and housing case
Insulation resistance: More than 50M at 1000V between electrical circuit and housing case
Dimension: 90 (L)*137 (W) *40 (D) mm
Weight: 330g
- Accessories: 7025 (Test Leads)
- 9067 (Pouch for test lead)
- Neck Strap
- R6P (AA) *4
- Instruction Manual
ADVANCE SCIENCE & TECHNOLOGY ZONE
We are the best supplier of scientific and laboratory equipment in Bangladesh. You can find your goods and needs with us at a very affordable rate than others. After all we provide the best quality original products from the manufacturer’s worldwide.
Being that we always work for our customer satisfaction as it is our first priority. You are always welcome to submit any query to us any time or visit our website astzbd.com for products you are looking for as well as you can have a visit directly to our shop at the address below.
1st floor shop #13 kader tropical
10 shaid nazrul islam road, hatkhola, tikatoly Dhaka-1203
E-mail: astzbd@gmail.com, Website: WWW.ASTZBD.COM
Cell: +88 01329100999
+88 01329100998
Reviews
There are no reviews yet.