Description
The BL983322 is a compact, panel mounted, process controller for measuring electrolytic conductivity (EC) of a process stream. The device features a large LCD with protective cover. Users may choose from automatic or manual dosing modes. When in automatic mode the dry contact relay is activated when a reading is above the set point. The relay can be used to activate a solenoid that switches from one DI (deionized) tank to another or to open a valve that will allow lower EC water to flow into a tank being monitored in order to lower its EC. The BL983322 can also be used to monitor the quality of water from DI tanks or from a distillation apparatus. The BL983322 measures EC from 0.00
Specification |
Detail |
|---|---|
| SKU | BL983322 |
| EC Range | 0.00 to 19.99 μS/cm |
| EC Resolution | 0.01 μS/cm |
| EC Accuracy (@25°C/77°F) | ±2% F.S. |
| Temperature Compensation | automatic from 5 to 50°C (41 to 122°F) with ß =2%/ºC |
| Calibration | manual, with CAL trimmer |
| Dosing Relay | maximum 2A (fuse protected), 250 Vac, 30 VDC contact closed when measure > setpoint |
| Setpoint | adjustable from 0 to 19.99 μS/cm |
| Overtime | adjustable, typically from 5 to approximately 30 minutes |
| Power Supply | models ‘-0’: 12 VDC adapter (included) models ‘-1’: 115/230 VAC 50/60Hz |
| Dimensions | 83 x 53 x 99 mm (3.3 x 2.1 x 3.9′) |
| Weight | models ‘-0’: 200 g (7.1 oz.) models ‘-1’: 300 g (10.6 oz.) |
| Ordering Information | Supplied with mounting brackets, transparent cover and instruction manual. |
| Recommended Probe | HI7634-00 EC/TDS probe with internal temperature sensor and 2 m (6.6′) cable (not included). |